4 - 20 mA Transducer

Self-Powered with 0.333 V Output

Product Image

Description: The MGT-0420-001 signal transducer offers inexpensive yet accurate true RMS monitoring of any AC voltage signal in the range of 0-333 mVolt.
This product is ideal as a precision 4 - 20mA transducer for use with Magnelab current transformers and voltage transformers that output 333mV full scale.
This transducer helps to reduce inventory by allowing the measurement of various signals by simply changing the input device

Features:

  • Power: Standard 4 - 20 mA loop, voltage 8 - 35 VDC
  • Input: 0-333 mV full scale AC voltage via input spade connectors
  • Output: 4 - 20 mA loop (sinking) Max. impedance 750 ohm @ 24 VDC (barrier strip terminal provided)
  • Accuracy: True RMS, 0.3% FS, up to crest factor 4
  • Input Frequency: 40 to 3,000 Hz
  • Enclosure: Potted pl", H = 0.54" 
Part Number and Rating
MGT-0420-001
0.333 Input

Magnelab, Inc.

600 Weaver Park Rd
Longmont, CO 80501
T: (303) 772-9100
F: (303) 772-9400
E: info@magnelab.com